Electric Valve: Complete Buyer’s Guide (2026)
An electric valve is a valve whose opening, closing, or intermediate position is driven by an electric actuator rather than a handwheel or a spring. That definition is easy. Choosing one is not.
Search the term, and you get four thousand product listings and almost no procedure. The pages that rank will tell you that a ball valve has a rotating ball. None of them will tell you what torque to ask for, which flow characteristic to specify, or what leakage class your specification should name. Fewer still explain why the valve installed last spring now hunts through every afternoon.
This guide covers electric valves for HVAC and industrial water and steam service. A sprinkler or irrigation “electric valve” is a solenoid with no actuator and no modulating control, which is a different device and a different article.
What follows is a buying procedure, not an encyclopedia. Six decisions, taken in order, each with the numbers that make it: use, body type, torque, flow characteristic, shut-off class, and control method. Work through them once, and you can write the specification yourself.
Key Takeaways
- Selection runs in a fixed order: use, body, torque, flow characteristic, leakage class, control signal. Skipping a step is how valves end up mis-applied.
- Throttling versus on/off decides everything downstream, including trim, actuator and cost. It is the first real fork, not a detail.
- Size an actuator on breakaway torque, then apply a margin of roughly 1.25 to 1.5 times. Running torque alone is the classic sizing error.
- Valve authority below roughly 0.3 makes a modulating valve hunt regardless of controller quality, and oversizing is the usual cause.
- Leakage class and the de-energised position are specification items. Neither has a safe default.
What Is an Electric Valve?

An electric valve is a valve assembly in three parts. A body that the fluid passes through. An actuator that moves the closure. A control signal that tells the actuator where to go. Everything else in this guide is about getting those three parts to agree with each other.
The mechanical arrangement varies. A quarter-turn body rotates a ball or a disc through 90 degrees. A linear body lifts a plug off a seat. In both cases, the actuator’s job is the same: turn an electrical command into a repeatable position, and hold it against whatever differential pressure the system applies.
If the actuator is the part you are specifying today, explore our electric valve actuators for motor and gear-train detail. This page stays with the decision.
Electric valve, electric control valve, motorized valve, MOV: one object, four names
Let’s start with the easy part. The trade uses several names for the same assembly, and the differences between them are about precision rather than hardware.
“Electric control valve” is the precise term when the valve is expected to hold an intermediate position and modulate flow. “Motor operated valve,” usually shortened to MOV, is the process-industry term and most often implies on/off duty with an end-limit switch. “Motorized valve” is the common North American synonym for the whole family.
British English uses “motorised valve,” and that spelling isn’t a footnote. UK search demand for “motorised valve” runs several times higher than for “electric valve,” so a page that ignores the spelling is invisible to a large English-speaking market. Same device, same actuator, one letter apart.
What an electric valve is not
Four devices get confused with it, and naming them saves a specification error later.
A solenoid valve uses an electromagnet to pull a plunger. It has two states, no actuator, and no ability to hold an intermediate position. Irrigation and sprinkler “electric valves” belong in this group.
A pneumatic valve drives its stem from compressed air. It needs a compressor and tubing, but in explosive atmospheres and at very high cycle rates it remains the better engineering choice. The US Department of Energy’s Building Technologies Office tracks how much of a building’s load sits in controls like these.
A pressure-independent control valve regulates its own flow against pressure changes without an external signal, so it needs no actuator at all.
A manual valve needs a person.
When an electric valve is the wrong buy
An electric valve is the default for HVAC water service because it needs only a power connection and a control signal. Three cases argue against it.
Where the atmosphere is explosive, a spark-free pneumatic actuator is usually required, and an electric actuator becomes a certification problem. Where the valve will cycle many times per hour, every hour, duty cycle becomes the limiting factor on life, and pneumatic actuation is often cheaper across the maintenance interval.
Where the branch flow is constant and only needs to be set once, a balancing valve or a pressure-independent valve does the job with no power at all. Buying an actuator for a branch that never modulates is a recurring cost with no control benefit.
Electric Valve Types by Body and Duty
The body is the second decision, and it is driven by the first: what the valve has to do. Isolation, modulation, and terminal-unit control want different bodies, and the difference shows up in cost, size, and controllability.
Quarter-turn bodies: ball and butterfly
A ball valve rotates a bored sphere against a seat. Full-bore ball valves offer high flow with low pressure loss and close tightly, which makes them the natural choice for isolation and for dirty, viscous, or two-phase media. Segmented and V-port versions add a shaped opening that can throttle reasonably well.
A butterfly valve rotates a disc inside the pipe. It occupies very little face-to-face length and costs less per unit of diameter, which is why it dominates large-bore isolation. Disc and seat material decide whether it seals well enough to hold.
Both are suited to electric ball valves in DN15 to DN300, with larger sizes built to order, and to electric butterfly valves in DN50 to DN500 for PN16 service. Black Ant ball valve actuators run on AC220V or DC24V. They’re IP65 as standard, with IP67 and IP68 available, and they come in 20 mm stroke for DN15 to DN50 and 40 mm stroke for DN65 to DN150.
Linear bodies: globe and single-seat
A globe valve lifts a plug off a seat, and the flow path turns twice on the way through. That tortuous path costs pressure and buys controllability. The plug can be shaped, guided and trimmed, and it holds position across the stroke far better than a rotating closure does.
This is why the globe body owns throttling service at moderate diameters. It is slower to stroke, it needs more torque, and it costs more than a butterfly of the same size. If the duty is modulation rather than isolation, those are acceptable trade-offs. For a detailed comparison, please see our article on globe valve vs ball valve.
Black Ant electric globe valves run DN15 to DN150 at PN25, with equal-percentage and linear characteristics and 4–20 mA or 0–10 V analogue input, with RS485 and Modbus available.
Miniature bodies for terminal units
The highest-volume electric valve application in any building is the fan coil terminal unit, and it is also the one most often specified carelessly. Miniature electric ball valves run DN8 to DN40 in two-way and three-way configurations, and they spend their whole lives cycling against a coil.
The savings case is large. Cooling already accounts for nearly 20% of the electricity used in buildings worldwide and about 10% of all global electricity consumption, according to the International Energy Agency. A terminal valve that cannot hold position wastes part of that load every hour of the cooling season.
A note on gate valves
An electric gate valve is a real product and a poor control valve. A gate slides across the flow and is designed to be fully open or fully closed. Using one to modulate produces vibration, seat damage, and terrible control at low flow. Specify gate valves for isolation and nothing else.
For a detailed comparison, please see our article on butterfly valve vs gate valve.
Body type selection table
| Body type | Black Ant range | Motion | Pressure class | Throttling | Best duty | If mis-applied |
|---|---|---|---|---|---|---|
| Ball | DN15 to DN300 (larger to order) | Quarter-turn | PN16 / PN25 | Fair; good with V-port or segmented trim | Isolation, tight shut-off, dirty or viscous media | Modulates poorly on a standard port; seat and ball wear at part-open |
| Butterfly | DN50 to DN500 | Quarter-turn | PN16 | Fair at large diameter | Large-bore isolation, changeover, AHU and chiller isolation | Disc sits in the flow path; throttling near closed is unstable |
| Globe | DN15 to DN150 | Linear | PN25 | Excellent | Modulating coil, steam, pressure control | Costs more and strokes slower than the duty needs |
| Single-seat | Model-dependent | Linear | Model-dependent | Excellent, balanced trim | Tight control at higher differential pressure | Over-specified where a standard globe would serve |
| Miniature | DN8 to DN40 | Quarter-turn | Model-dependent | Fair | Fan coil and terminal units, 2-way and 3-way | Undersized actuator stalls on coil differential |
Ranges above are the published Black Ant figures. Confirm the pressure class and trim against the current datasheet before writing them into a project specification.
For more information, please read our article on V-port ball valves.
Throttling or On/Off? The First Fork

Throttling means holding an intermediate position in response to a signal. On/off means driving to an end stop. The physical difference lies in the trim and the actuator, and it changes the price of everything that follows.
What on/off service needs
On/off duty is isolation, zone enable, seasonal changeover, and safety shut-off. The actuator needs to reach a limit and stop, so it needs no positioner and no proportional input. A feedback contact is useful to prove position but not essential to function.
Because the actuator never holds an intermediate position, wear is concentrated at the seats. Cycle count is the life-limiting factor, not modulation accuracy.
What throttling service needs
A throttling valve is one asked to hold an intermediate position. Throttling service means coil control, temperature and flow modulation, and anything with a control loop behind it. The actuator must accept an analogue or bus command, hold position against differential pressure, and usually report back.
A modulating valve also has to be characterised. Its inherent flow curve has to compensate for the coil’s own behaviour, which is the subject of the flow characteristic section below. Skipping that step produces a valve that controls nothing well.
To obtain a detailed comparison, please see our article on throttling valve vs control valve.
The cost of choosing wrong
The same error repeats every commissioning season. A facilities engineer, call her Dana, inherits a terminal-unit retrofit with eighty fan coils on one riser. The valves are on/off, the new controller drives them with 0–10 V, and the third-floor rooms swing either side of setpoint while the plant runs flat out. Nothing in the building is broken. The valves were bought for isolation and are being asked to modulate.
Two things then happen. The loop gets blamed, so somebody retunes a controller that was never the problem. And the actuator duty cycle fails early, because it is now stroking continuously in a product designed to stroke occasionally.
The reverse error is quieter and costs more. A modulating valve on a duty that only needed isolation means paying for a positioner, a proportional signal and a characterised trim that nothing uses. Across those same eighty terminal units, that’s eighty avoidable upgrades.
For more information, please read our article on cage-guided control valves.
Duty mode table
| Duty | Actuator type | Control signal | Feedback | Typical application | Common mistake |
|---|---|---|---|---|---|
| Isolation | On/off, spring return optional | 2-point, or 3-point floating | Optional position proof | Coil isolation, chiller isolation, changeover | Specifying a modulating actuator for a duty that never modulates |
| Zone enable | On/off | 2-point | Recommended | Branch or zone shut-off, night setback | Omitting feedback, then commissioning blind |
| Modulating coil control | Proportional or bus | 0–10 V, 4–20 mA, Modbus, BACnet | Required for verification | AHU and fan coil coils, reheat | Buying on/off and driving it with an analogue signal |
| Pressure or flow control | Proportional | 4–20 mA | Required | Pressure sustaining, flow limiting | No authority check before selection |
| Safety shut-off | Fail-safe | 2-point, de-energise to act | Required | Fuel, steam, freeze protection | Assuming fail-safe without specifying stored energy |
Electric Valve Torque, Actuator Sizing and Control Signals
Torque is where selection stops being qualitative. An actuator that cannot overcome the load at the worst moment stalls at the worst moment, usually the first cold morning of the season.
The loads torque has to overcome
- Breakaway torque. Static friction at rest, before anything moves. Always the highest of the friction loads.
- Running torque. Dynamic friction while the closure travels. Lower than breakaway, and the number most often quoted.
- Seating torque. The extra force needed to press the closure into the seat and achieve the specified leakage class.
- Differential pressure load. The force the pressure difference applies across the closure, which rises with diameter and with the pressure drop the valve is throttling.
- Packing and stem friction. Small when new, larger when hot, and larger again after a few thousand cycles.
The safety factor
Size the actuator on breakaway torque, then add a margin. A common rule of thumb is 1.25 to 1.5 times, with the higher end for high differential pressure, high temperature, or media that deposits on the stem.
Sizing on running torque alone is the classic error. It produces a valve that works perfectly in the workshop and stalls in service, when packing has stiffened, and the differential is at its design maximum. This is industry practice rather than a figure from a standard, so treat the margin as a starting point for engineering judgement.
Duty cycle decides the motor
How often the valve moves is a separate question from how hard it has to push, and it decides the actuator class.
A zone valve that opens once in the morning and closes once at night is a different product from a coil valve that repositions every few minutes through the cooling season. The gearbox, the motor winding and the rated life all follow from the cycle count. Specify cycle life against the cycles the building will actually demand, not against calendar age.
Control signals, feedback and protocols
Four signal families cover most HVAC and industrial work.
Two-point control drives the valve fully open or fully closed from a contact. Three-point floating control drives it open or closed from two contacts and infers position from travel time.
Proportional control uses 0–10 V or 4–20 mA to command a position, and needs a positioner or an analogue-capable actuator to hold it.
Bus control puts the valve on the building network as a device rather than a loop element. Black Ant actuators offer 4–20 mA, RS485, and M-Bus, with Modbus and HART available. That covers what a building automation system usually needs: to read valve position rather than infer it.
Feedback matters more than most specifications admit. Without a position signal, commissioning becomes an exercise in assumption, and a stuck valve looks exactly like a satisfied load.
To learn more information, please read our article on normally open vs normally closed valves.
Torque and actuator selection table
| Load component | How it arises | When it dominates | Sizing treatment |
|---|---|---|---|
| Breakaway | Static friction at rest | Cold start, long idle periods, deposited media | Size the actuator on this figure |
| Running | Dynamic friction in travel | Continuous modulation | Compare against rated running torque |
| Seating | Closure pressed into seat | Tight leakage classes required | Add seating allowance on top of running |
| Differential pressure | Pressure difference across closure | High ΔP, large diameter, near-closed throttling | Calculate at design ΔP, not at shut-off head |
| Packing and stem | Gland friction, thermal growth | High temperature, aged packing | Covered by the safety margin |
For a deep understanding, please read our article on valve torque and actuator sizing.
Flow Characteristics, Kvs and Valve Authority

Once the valve can move, the question becomes how it should move. Two numbers answer it, and the second is missing from almost every guide on the English side of this subject.
Equal percentage, linear and quick open
An equal-percentage characteristic adds a constant percentage of the current flow for each increment of travel. At low lift, the flow changes slowly, and at high lift it changes quickly. That shape happens to compensate for the behaviour of a heating or cooling coil, which transfers most of its capacity in the first part of its flow range. This is why equal percentage is the default for coil control.
A linear characteristic changes flow by a constant amount per unit of travel. It suits constant-pressure-drop loops and level control, where the relationship between position and flow is already straight.
A quick-open characteristic delivers most of its flow in the first part of the stroke and then flattens. It suits service that is close to on/off but benefits from a softer seat approach. It does not suit modulation.
To learn more technical information, please read our article on control valve flow characteristics.
Kvs and rangeability in plain English
Kvs is the flow in cubic metres per hour of water that passes through a fully open valve at a pressure drop of one bar. It is a single number that lets you compare a DN15 valve against a DN50 valve, and against a competitor’s DN15 valve, on the same basis.
Cv is the same idea in US customary units, expressed in gallons per minute at one psi drop. The relationship between Kvs and Cv is a fixed constant, and both are legitimate as long as you do not mix them mid-calculation.
Rangeability is the ratio of maximum to minimum controllable flow. A valve with wide rangeability holds control at low load, which matters in a variable-flow system where most hours are part-load hours. Our control valve sizing guide works the Kvs arithmetic in full.
Valve authority, the number nobody publishes
Valve authority is the share of the circuit’s total pressure drop that falls across the valve at design flow:
N = Δp valve ÷ (Δp valve + Δp rest of circuit)
The number that matters is its size. Above roughly 0.5, the valve has good authority, and its characteristic means what the datasheet says. Between 0.3 and 0.5, it is workable. Below about 0.3, the valve cannot shape the flow it is trying to control, and the loop will hunt no matter how well the controller is tuned.
Take the arithmetic a consultant would actually do. A chilled-water coil circuit has 30 kPa across the control valve and 70 kPa across the rest of the circuit at design flow. Authority is 30 divided by 100, or 0.3. That is the bottom of the acceptable band, and the honest recommendation is a smaller valve, not a better controller.
Call the engineer who inherited that schedule, Ana. One size down, the valve carries more of the circuit drop and sits further open at design flow, where its characteristic is closest to the curve the datasheet promises. The coil that used to overshoot at part load holds setpoint. Nothing was returned, and nothing was replaced.
Oversizing is the usual cause. A valve too large for the flow runs nearly closed at design conditions, where its characteristic is steepest and least stable. The instinct to add margin to the valve size produces the exact instability the margin was meant to prevent.
For a deeper look, please read our article on valve authority explained.
Characteristic and authority table
| Characteristic | Curve shape | Where it belongs | Authority sensitivity | Symptom when wrong |
|---|---|---|---|---|
| Equal percentage | Slow at low lift, fast at high lift | Coil control, heating and cooling | Moderate | Coil overshoots at low load, then lags |
| Linear | Constant flow change per unit travel | Constant ΔP loops, level control | High | Instability as soon as circuit ΔP varies |
| Quick open | Most flow in first third of stroke | Near on/off with soft seating | Low | Cannot hold part load at all |
| Authority (N) | Assessment | Action |
|---|---|---|
| 0.5 and above | Good | Proceed with the selected characteristic |
| 0.3 to 0.5 | Acceptable | Check part-load behaviour, consider one size down |
| Below 0.3 | Poor | Re-select smaller, or reduce circuit drop |
Shut-Off Class, NO vs NC and Fail-Safe
Two specification items decide what happens when the valve is closed and what happens when the power fails. Neither has a safe default, and both are routinely left off the schedule.
Leakage classes
The ANSI/FCI 70-2 class system grades how much a closed valve may leak. Class I sets no specific limit beyond the manufacturer’s own standard. Class VI is bubble-tight under a defined test. Classes II through V step down between them.
Class IV is the ordinary commercial HVAC specification for a control valve. Class VI is what a chilled-water isolation valve usually needs, because a leaking isolation valve defeats the point of isolating.
The material choice matters as much as the number. A metal-seated globe valve and a soft-seated ball valve reach very different classes at similar cost, and no amount of specification writing changes what the seat can do.
Normally open and normally closed
NO and NC are defined by the de-energised state, which is what the valve does when power is lost. This is why the terms belong on the drawing and not only in the actuator datasheet.
Normally closed is the default for a heating or cooling coil valve. When power fails, the coil is isolated, and no uncontrolled energy enters the space. It is also the right choice anywhere an open valve on power loss would be a hazard.
Normally open is for freeze protection, safety venting, and any duty where the safe state is flowing. A heating coil in a space that must not freeze wants its valve to open when the power drops.
Specifying the wrong one is not a small error. A building full of NC coil valves loses its freeze protection the moment the electrical supply does.
Fail-safe and stored energy
A fail-safe actuator returns the valve to a defined position without power, using spring return, capacitor return, or battery return. Each has a cost, a response time, and a duty-cycle penalty.
A spring-return actuator is the most predictable, but it takes actuator torque to compress the spring on every stroke. A capacitor or battery return keeps the actuator smaller, at the price of stored energy that ages and must be proven.
Fail-safe is a product variant, not a setting. Specify it, then test it at commissioning by actually removing power.
Cavitation is a selection error, not a wear problem
Cavitation begins when the local pressure inside the valve falls below the fluid’s vapour pressure and bubbles form, then collapse as pressure recovers downstream. Flashing is the same onset with no recovery, and it produces two-phase flow instead of noise.
The symptoms arrive as a specification failure. Noise and vibration appear at high lift. The seat erodes. The control loop gets worse as the valve opens, because the flow no longer follows the characteristic at all.
The fixes are all selection-level. Use a body with lower pressure recovery, such as a globe or a cage-trim design. Run the valve further open by selecting a smaller. Stage the pressure drop across two valves, or specify hardened trim where cavitation can’t be avoided. Replacing like with like fixes nothing.
For detailed information, please see our article on valve positioner vs actuator.
Leakage class table
| Class | Allowable leakage | Typical seating | Where specified |
|---|---|---|---|
| I | No specific limit; manufacturer’s standard | Metal, minimal | Non-critical shut-off, low hazard |
| II | Small percentage of rated capacity | Metal | General isolation where some seepage is tolerable |
| III | Roughly one fifth of Class II | Metal, lapped | Better-than-ordinary isolation |
| IV | Small fraction of rated capacity | Metal or soft, lapped | Standard HVAC control valve specification |
| V | Very small, measured by a defined test | Soft, high-integrity | Chilled water, glycol, costly media |
| VI | Bubble-tight under the defined test | Soft, resilient | Isolation that must truly isolate |
Class descriptions are the standard designations, summarised. Confirm the figures against the ANSI/FCI 70-2 edition your specification cites before publishing them in a schedule.
To learn more information, please read our article on control valve leakage classes.
NO and NC fail-state table
| Configuration | De-energised state | Power-failure consequence | Typical application | If specified backwards |
|---|---|---|---|---|
| NC | Closed | Coil isolated, no energy enters | Heating and cooling coil valves, terminal units | Freeze protection lost; uncontrolled energy on failure |
| NO | Open | Flow continues | Freeze protection, safety venting, cooling where stagnation is unsafe | Coil isolated on failure; freeze or overheat risk |
| Fail-safe return | Defined position, spring or stored energy | Actuator drives to the defined position | Isolation with a mandatory safe state | Assumed safe state that the actuator cannot reach |
The fail-safe depth lives in our fail-safe control valve article. This page only tabulates the decision.
When a Valve Misbehaves, and the Ten-Item Checklist

This section turns the guide into something you can carry into a project meeting.
What to fix when a valve misbehaves
Four symptoms account for most electric valve problems in service, and each points back to a selection step rather than a maintenance task.
A valve that hunts has an authority problem or a characteristic mismatch. Check authority before touching the controller.
A valve that cannot reach design flow was sized on a differential that does not match the circuit, or the pump curve was read at shut-off head.
A valve that leaks when closed has the wrong leakage class for the duty, or a metal seat where a soft seat was needed.
A valve that stalls or fails to stroke was sized on running torque, or its duty cycle was never checked against the cycle count.
The ten-item selection checklist
Work in this order. Each item rules something out, and the order is the point.
- Medium and temperature. Water, glycol, steam, or something else, and at what temperature.
- Design flow and differential pressure. Not pipe size, and not shut-off head.
- Throttling or on/off. The fork that decides trim and actuator.
- Body type and nominal diameter. From the duty, then checked against the table above.
- Pressure class. PN16 or PN25, matched to the circuit’s working pressure.
- Kvs and flow characteristic. Sized on flow and chosen on what the coil needs.
- Valve authority check. Below roughly 0.3, go back to item 4 and re-select smaller.
- Leakage class. Class IV for control, Class VI for isolation that must isolate.
- NO or NC, and fail-safe. Defined by what the building needs on power loss.
- Control signal and protocol. 0–10 V, 4–20 mA, RS485, Modbus, BACnet or M-Bus, matched to the controller that will drive it.
What to demand from a supplier
The checklist doubles as a buying test. Ask any supplier for seven things, and treat a vague answer as an answer.
- Documented Kvs for the model offered.
- A stated leakage class, not a reassurance.
- Actuator torque at the differential pressure you specified, not a generic figure.
- The IP rating.
- A duty-cycle or cycle-life rating.
- The protocol list, in writing.
- The pressure class on the body, not in a footnote.
Black Ant publishes the DN ranges, voltages, stroke lengths, IP ratings, and protocol options for its electric valve range. Torque and Kvs figures per model are available on request through our application engineers, and that request is exactly the test this section describes. Being asked for the numbers is how a specification gets written properly.
That’s also where custom work starts. Ball valves above DN300 are built to order. IP67 and IP68 actuators cover washdown and outdoor installation. M-Bus and Modbus handle building automation integration, and OEM actuator voltage variants are available for private-label programs.
If you’re working through the checklist for a live project, contact our application engineers with the duty and the differential. The sizing can usually be settled in one exchange.
Frequently Asked Questions
Is an electric valve the same as a motorized valve?
Yes. Electric valve, motorized valve, and motorised valve describe the same assembly: a valve body driven by an electric actuator. “Motor operated valve” and MOV are the process-industry variants of the same term. The differences are regional and idiomatic, not mechanical.
What is the difference between an electric valve and a solenoid valve?
A solenoid valve uses an electromagnet to move a plunger. It has two states, open and closed, with no actuator and no way to hold an intermediate position. An electric valve uses a motorized actuator and can modulate. Irrigation and sprinkler valves sold as “electric valves” are solenoids.
How do I choose the right electric valve size?
Size on design flow and the pressure drop you want across the valve, not on pipe diameter. Then check valve authority. A valve carrying less than about 30% of the circuit’s design pressure drop will struggle to control flow, whatever its nominal size.
What do NO and NC mean on an electric valve?
They describe the valve’s position when the actuator is de-energised. Normally closed shuts on power loss, which is the usual choice for a coil valve. Normally open opens on power loss, which is what freeze protection and safety venting require.
Do electric valves need a positioner?
Only if the valve must hold an intermediate position from a proportional or bus signal. An on/off valve needs no positioner. A feedback signal is worth having either way, because without it, commissioning can’t confirm that the valve went where it was told.
How long do electric valve actuators last?
Life is set by cycle count, not calendar age. A modulating actuator that repositions continuously and a zone actuator that strokes twice a day are different products with different rated lives. Specify against the cycles the building will actually demand.
Conclusion
Six decisions, in order. What the valve must do. Which body suits it. How much torque the actuator needs. Which flow characteristic the coil wants. What leakage class the duty requires. And how the valve will be told what to do.
Each one rules something out before the next begins. Work them in that order, and the specification writes itself.
Almost every electric valve problem in a building is a selection problem, not a manufacturing one. Almost every selection problem is one of four: wrong duty, wrong torque, no valve authority, or an unspecified leakage class. All four are cheaper to fix on a schedule than in a plant room.
If you’re specifying for a project, browse our electric control valve range by body type. Then put the duty and the differential in front of an application engineer and let the sizing be checked before the order goes out. That sequence costs an email. Getting it wrong costs a season.