Valve Authority Explained: Why Half Travel Is Not Half Flow

Valve authority is the pressure drop across a fully open control valve divided by the pressure drop across its whole circuit at design flow. It is a ratio between 0 and 1, and it decides how much of the valve’s stroke does useful work.

The consequence is easy to miss. At an authority of 0.17, a linear valve passes about 82% of design flow at half travel. The last half of the stroke does 18% of the work, and the controller spends most of its life in the first third of its signal. Nothing is broken. The valve is simply too large for the circuit it ended up in.

That number is not printed on the valve. You create it when you choose the Kvs, and lose it again when you round to the nearest catalogue size. This article gives the formula, the bands, the installed curve, and a method for landing between 0.3 and 0.5 with a valve you can buy.

Sizing a schedule now? Start with the control valve sizing guide → and come back for the authority check.

Key Takeaways

  • Valve authority is ΔP across the fully open valve divided by ΔP across the whole circuit at design flow. Change the boundary and the number changes.
  • It is a property of the valve in its circuit, not of the valve alone.
  • Low authority bends the installed curve. At an authority of 0.2 a linear valve passes about 79% of design flow at half travel; at 0.1 it passes 88%.
  • The 0.5 target is a compromise between controllability and pump energy, not a code requirement. 0.3 to 0.5 is the practical band.
  • The Kvs you buy decides the authority you get. Recompute after rounding to the nearest stock size.

What Valve Authority Means

What Valve Authority Means
What Valve Authority Means

Authority describes how much of the circuit’s total pressure drop belongs to the valve when it is fully open at design flow. If the valve owns most of the drop, it can shape flow over its whole stroke. If it owns very little, the rest of the circuit dominates and moving the plug changes flow far less than the catalogue curve suggests. It is written N, sometimes β.

The Valve Authority Formula

The formula is a ratio of two pressure drops:

N = ΔPv / (ΔPv + ΔPc)

  • ΔPv is the valve authority pressure drop, measured across the fully open valve at design flow.
  • ΔPc is the pressure drop across everything else at the same flow: coil, pipe, fittings, strainer, isolation valves, balancing valve, differential-pressure controller.

Both are taken at the same design flow; otherwise the numbers are not comparable. If you know the valve’s Kvs, ΔPv comes from the catalogue equation:

ΔPv = (Q / Kvs)²

with Q in m³/h and ΔPv in bar.

Which Circuit? The Denominator Problem

The formula is simple. The denominator is not. One convention takes the circuit as the valve plus the coil:

N = ΔPv / (ΔPv + ΔPcoil)

Common in fan-coil literature. The other takes the whole branch and adds pipe, fittings, and balancing. The second predicts the curve the loop will actually see, because every one of those pressure drops changes the flow through the valve. Some guides write “valve plus coil” and mean the rest of the branch; read literally, authority is overstated.

The gap is not academic. Take a valve dropping 12 kPa at design flow, a coil dropping 15 kPa, and pipe, fittings, and balancing dropping another 8 kPa:

Boundary Calculation Authority
Valve + coil only 12 / (12 + 15) 0.44
Whole branch 12 / (12 + 15 + 8) 0.34

Same valve, same coil, same flow: one convention calls it comfortable, the other marginal. State the boundary.

Why the Same Valve Has a Different Authority in a Different Branch

Because the denominator includes the rest of the circuit, authority is not a fixed property of a product. Put the same Kvs 2.5 valve, passing the same 0.86 m³/h, into a branch with 45 kPa of coil and pipe loss instead of 23 kPa:

  • 11.8 / (11.8 + 23) = 0.34
  • 11.8 / (11.8 + 45) = 0.21

This is why a valve that worked in one building can hunt in another. The valve did not change; the circuit got longer, the balancing valve got throttled, or the coil was selected with a higher drop.

Control Valve Authority and the Installed Characteristic

Control Valve Authority and the Installed Characteristic
Control Valve Authority and the Installed Characteristic

A control valve has two curves. The inherent characteristic is measured at a constant pressure drop across the valve and is the curve printed in the catalogue. The installed characteristic is what the loop sees when the pressure drop across the valve falls as flow rises.

Authority sets how far one drifts from the other. At 1.0, the curves match; at 0.1, the installed curve is badly distorted.

The Table: Flow at Half Travel for Seven Authorities

This is the number worth remembering. Flow is given as a percentage of design flow, with the total branch pressure drop held constant.

Authority N Linear: flow at 50% lift Equal % (R = 50): flow at 50% lift Linear: lift needed for 50% flow Linear: flow at 10% lift
1.00 50.0% 14.1% 50.0% 10.0%
0.70 56.8% 16.8% 43.5% 11.9%
0.50 63.2% 19.8% 37.8% 14.1%
0.30 72.5% 25.2% 30.2% 18.0%
0.25 75.6% 27.5% 27.7% 19.7%
0.20 79.1% 30.4% 25.0% 21.9%
0.10 87.7% 41.2% 18.0% 30.3%

Values from the standard installed-characteristic model described below. They are computed, not tested, product data.

Three things fall out of the table. Half travel is not half flow, and the gap widens as authority falls: a linear valve at authority 0.2 is already at 79% of design flow when half open. The elbow moves too: at authority 0.1 the same valve reaches half flow at 18% lift, where a small signal change produces a large flow change. And the gain at the bottom of the stroke rises as 1/√N, so a loop tuned at design load will be too aggressive at low load.

The Model Behind the Table

The linear column comes from q = x / √(N + (1 − N)x²) and the equal-percentage column from q = R^(x − 1) / √(N + (1 − N)R^(2x − 2)), where x is fractional lift, q is fractional flow, and R is rangeability, taken as 50. At part load, the valve’s share of the total drop falls with the square of flow, so the same lift produces less flow than the catalogue promises.

The model assumes a constant branch pressure drop, turbulent flow, the named inherent characteristic, no cavitation, and a linear actuator. Real installations depart from all five.

The arithmetic checks out. At N = 1.0, the model reproduces both inherent curves exactly, including 14.1% at half travel on a 50:1 equal-percentage trim. Against a manufacturer’s measured curve, the shape should match; the exact numbers will not, because a catalogue curve is tested, not modelled.

To obtain a detailed comparison, please see our article on throttling valve vs control valve.

Where the Authority Bands Come From

The bands are conventions, not physics. They come from commissioning experience, and they are consistent across sources.

Authority Control quality What it looks like on site
0 – 0.25 Unstable to fair Hunting, on/off behaviour, actuator wear
0.25 – 0.50 Fair to good Workable, but the loop is sensitive at low load
0.50 – 1.00 Good to excellent The installed curve stays close to the catalogue curve

FlowCon, a Danish PICV manufacturer, states the same three bands and then adds the sentence that matters most for selection:

“For practical purposes control valves are commonly selected to have an authority of 35-75% providing a fair compromise between control and energy consumption.”

That is the honest version. The top of the band is not free.

0.5 Is a Compromise, Not a Law

Every kilopascal the valve drops at design flow has to come from the pump. Push authority from 0.3 to 0.5, and the valve gets smaller, the drop across it gets larger, and the pump works harder for the same flow. Control improves. Energy consumption does not. A valve at 0.8 controls beautifully and wastes pump energy for the life of the building; a valve at 0.25 is harder to tune and cheaper to run. The 0.35 to 0.75 range is the compromise most guidance settles on; 0.5 is its midpoint, not a requirement.

The 0.25 Floor and the Design/Minimum Rule

A TA Hydronic College presentation at the Rocky Mountain ASHRAE 2013 technical conference sets two rules rather than one: design for at least 0.5, and check that the minimum at part load stays above 0.25. It also gives the sizing condition behind the floor:

ΔPv ≥ (ΔPpipe + ΔPc) / 3

Substitute that into the formula, and you get N ≥ 0.25 exactly. It is the point where the installed curve has bent far enough that tuning becomes unreliable. The word “minimum” is doing real work in that sentence.

Design Authority Is Not Operating Authority

Design Authority Is Not Operating Authority
Design Authority Is Not Operating Authority

Authority is calculated at design flow; buildings spend most of their time elsewhere. Without differential-pressure control, the pressure at a branch rises as other branches close, so the valve’s share of it falls. The design number is the best case, not the normal case.

The same TA Hydronic College deck shows a valve designed at 0.5 landing at 0.23 at half load. The valve has not changed. The circuit has. This is the mechanism behind the most common commissioning complaint in hydronic systems: the loop was stable at handover and hunts every evening a year later.

When a DPCV or PICV Holds the Denominator Steady

A differential-pressure control valve holds a fixed ΔP across the branch, so the valve’s share stays roughly constant as flow falls; the design authority survives part load. A PICV goes further: it combines flow limiting, balancing and differential-pressure control in one body, so the control element sees the full available differential above its minimum. That is what “100% authority” means, with one condition: below the minimum differential, the PICV stops regulating. Authority has moved into a pressure requirement. Our PICV range for fan coils is built on that principle.

Three-Way Valves: Authority Is Per Port

A three-way valve has two circuits through it, A–AB and B–AB, and each has its own authority. A single number cannot describe both. The three-way valve reference sets out the consequence: total flow through port AB stays constant only at an authority of 1, which is practically impossible, so every real three-way valve lets the total flow move as the stem travels.

How much it moves depends on the characteristic pair and the authority. For a total-flow deviation of about 10%, ter-en gives:

Characteristic pair Authority for ~10% deviation
Linear / linear 0.8 – 1.0
Equal percentage / linear 0.3 – 0.5
Equal percentage / equal percentage 0.1 – 0.2

A linear/linear three-way valve needs very high authority to behave; an equal-percentage pair tolerates much less. Size a mixing valve for a coil or changeover circuit and compute each port separately.

To learn more technical information, please read our article on control valve flow characteristics.

How to Hit 0.3–0.5 With Valves You Can Buy

The calculation is easy; the catalogue is hard. Kvs values follow a geometric series: 0.25, 0.63, 1.00, 1.60, 2.50, 4.00, 6.30, 10, 16. So the valve you can buy is rarely the one you calculated. A valve authority calculator will confirm the ratio, but it will not check which denominator you fed it or which Kvs actually exists. Authority is decided at the rounding step.

The Five-Step Method

  1. Find the design flow. Q = P / (1.163 × ΔT) for water, with P in kW, ΔT in K, and Q in m³/h.
  2. Add up the rest of the circuit. Coil, pipe, fittings, and balancing valves, all at design flow.
  3. Choose a target authority. 0.35 is a good default inside the 0.3–0.5 band.
  4. Solve for the valve drop and Kv. ΔPv = N / (1 − N) × ΔPc, then Kv = Q / √(ΔPv in bar).
  5. Round to the nearest Kvs and recompute. Then check the installed curve and the pump head, not just the ratio.

Step 5 is the one that gets skipped. It is also the one that decides what the building gets.

Worked Example: A 20 kW Coil Branch

Take a 20 kW cooling coil with a 20 K water temperature difference. The design flow is 20 / (1.163 × 20) = 0.86 m³/h. The coil drops 15 kPa at that flow; the pipe, fittings, and the balancing valve add 8 kPa. The rest of the circuit is 23 kPa.

With a target authority of 0.35, ΔPv = 0.35 / 0.65 × 23 = 12.4 kPa (0.124 bar), and Kv = 0.86 / √0.124 = 2.44. The nearest standard Kvs is 2.5. Recompute: ΔPv = (0.86 / 2.5)² = 11.8 kPa, and N = 11.8 / (11.8 + 23) = 0.34.

That lands inside the band. A linear trim passes 70.4% of design flow at half travel; an equal-percentage trim passes 23.8%. The latter feels slower at mid-stroke, which is the point of the curve.

Now try the neighbouring catalogue sizes. This is where the decision actually lives:

Kvs ΔPv at 0.86 m³/h Authority N Linear flow at half travel Pump-head consequence
1.6 28.9 kPa 0.557 61.2% +17.1 kPa at design flow
2.5 11.8 kPa 0.340 70.4% baseline
4.0 4.6 kPa 0.167 81.6% −7.2 kPa, but the loop gain rises sharply

One step up the series takes the valve from a comfortable 0.34 to 0.167, below the practical floor. One step down takes it to 0.557, which controls better and costs 17.1 kPa of extra pump head for the life of the building. Neither is automatically wrong. The point is that the choice is visible before the valve is ordered, and invisible afterwards.

The fan-coil version, including DN15 to DN25 selection, is in our fan coil valve sizing guide.

When Authority Does Not Apply

When Authority Does Not Apply
When Authority Does Not Apply

Authority is a modulating-control metric. It answers one question: will this valve be able to shape flow over its stroke? Some valves and duties are not asking that question.

PICVs and the Minimum Differential

A PICV is usually described as having 100% authority, and above its minimum differential is a fair description. Below the minimum, the regulator inside it stops working, and flow falls away. The number to check is the minimum differential at design flow, not the authority ratio.

On/Off and Self-Acting Valves

For a solenoid, a thermostatic radiator valve, a pressure-reducing valve, or a relief valve, authority does not apply at all. They are selected on close-off, capacity, set point, and response; the bands applied to them produce a number that looks rigorous and means nothing.

What Authority Cannot Fix

Authority will not cure cavitation, noise, a coil selected with the wrong temperature difference, a sensor in the wrong place, or the wrong characteristic for the load. And it is not free: every point of authority you add is pump energy you pay for. Authority tells you whether the valve can control. It does not tell you whether the rest of the design is right.

Frequently Asked Questions

What is a good valve authority?
Between 0.3 and 0.5 for most modulating hydronic valves. 0.5 is the usual design target, 0.25 is the practical floor, and 0.35 is a sensible default when the catalogue forces a choice.

Is 0.5 always the best value?
No. Higher authority improves controllability and increases pump energy. FlowCon’s practical band runs from 0.35 to 0.75 because 0.5 is a compromise rather than an optimum.

How do you calculate valve authority?
Divide the pressure drop across the fully open valve at design flow by the pressure drop across the whole circuit at the same flow: N = ΔPv / (ΔPv + ΔPc). If you know Kvs, ΔPv = (Q / Kvs)².

What happens when valve authority is too low?
The installed curve bends toward quick-opening. The valve does most of its flow change early in the stroke, loop gain rises, and the actuator hunts or cycles. At authority 0.1, a linear valve passes 88% of design flow at half travel.

Do PICVs really have 100% authority?
Above their minimum differential, effectively yes. Below it, no. Check the minimum differential at design flow rather than accepting the headline number.

Is valve authority the same as rangeability?
No. Rangeability is how wide a band of flow the valve can control; authority is how much of the circuit’s pressure drop the valve owns. Our guide to control valve rangeability covers the first.

The Number You Choose Before the Valve Arrives

Valve authority is not a specification you look up. It is the consequence of two decisions: how much pressure drop the valve is allowed to take, and which catalogue Kvs you buy. Get those right, and the installed curve stays close to the catalogue curve. Get them wrong, and no amount of controller tuning will recover the loop.

Three checks before the schedule is issued. State the circuit boundary, so the number means the same thing to everyone reading it. Recompute after rounding to the nearest Kvs, because that is where it is usually lost. And check the minimum at part load, not just the design value, because that is where the building operates.

If the numbers are close and the choice is not obvious, send us the duty and the circuit pressure drop. Our application engineers will work through the Kvs step with you and confirm the selection against the valve range. For the wider picture, the electric valve guide covers how the type, actuator, and characteristic fit together.