Equal Percentage Valve: Linear vs Quick-Opening Curves

An equal percentage valve changes flow by a constant percentage for each equal step of travel, which makes its curve logarithmic rather than straight. The practical consequence surprises almost everyone: on a trim with a 50:1 rangeability, half travel delivers about 14% of full flow, not 50%.

That isn’t a fault. It’s the whole design. The curve exists to cancel something else happening in the system, and until you know what that something is, the catalogues look like three arbitrary shapes. Each one answers a different question about the load.

By the end, you will know which curve your duty needs, why the catalogue curve isn’t the curve you commission, and what a different trim won’t fix. From a comprehensive perspective, the electric valve selection guide covers body type, torque, characteristic, and leakage class.

Choosing a trim for a live schedule? Start with our control valve sizing guide → and size the valve before the curve.

Key Takeaways

  • Equal percentage means equal percentage steps, not equal flow steps. At a 50:1 rangeability, 50% travel gives about 14% of full flow, and half flow arrives at about 82% travel.
  • Every 10% of travel multiplies flow by a fixed factor: 1.48 at a 50:1 trim, 1.58 at 100:1. That factor, not the shape of the graph, is what the name means.
  • The catalogue curve is measured at constant differential pressure. It is not the curve you commission.
  • At an authority of 0.8, an equal-percentage trim reaches half flow at about 80% lift. At 0.2, it reaches half flow at about 65% and behaves far closer to linear.
  • Equal percentage answers a curved load. It is not a universal default, and for a plain flow loop a linear trim is usually better.

What an Equal Percentage Valve Actually Does

What an Equal Percentage Valve Actually Does
What an Equal Percentage Valve Actually Does

An equal percentage control valve gives equal percentage changes in flow for equal increments of lift. Move the plug from 30% to 40% and flow rises by the same proportion as moving from 60% to 70%. The steps are equal in ratio, never in cubic metres per hour.

The Definition in One Equation

The curve is Q / Qmax = R^(x − 1), where x is fractional travel from 0 at closed to 1 at fully open, and R is rangeability, the ratio between the largest and smallest controllable flows. At x = 1, the expression returns R^0, which is 1, which is the only point where every rangeability agrees.

Printed as a table, the equation does what words cannot. This is the equal percentage valve curve that every catalogue is quoting:

Travel Linear Equal % R = 30 Equal % R = 50 Equal % R = 100
10% 10.0% 4.7% 3.0% 1.6%
20% 20.0% 6.6% 4.4% 2.5%
30% 30.0% 9.2% 6.5% 4.0%
40% 40.0% 13.0% 9.6% 6.3%
50% 50.0% 18.3% 14.1% 10.0%
60% 60.0% 25.7% 20.9% 15.8%
70% 70.0% 36.0% 30.9% 25.1%
80% 80.0% 50.6% 45.7% 39.8%
90% 90.0% 71.2% 67.6% 63.1%
100% 100.0% 100.0% 100.0% 100.0%

Values from the standard exponential model at constant differential pressure. They describe an idealised inherent characteristic, not a tested product.

Read the R = 50 column against the linear one, which is the whole of the equal percentage valve vs. the linear argument. At 50% travel, the linear valve is at 50% flow; the equal percentage valve is at 14%. It catches up only in the last quarter of its stroke, and between 10% and 30% travel it passes less than a tenth of capacity.

You can check the model against a published example rather than trusting it. Spirax Sarco’s worked Example 6.5.1 uses a valve with a maximum flow of 10 m³/h and a rangeability of 50, and gives 0.956, 1.414 and 2.091 m³/h at 40%, 50% and 60% lift. The equation above returns 0.956, 1.414, and 2.091.

Why Equal Percentage Is Not Equal Flow

Divide the flow at one travel point by the flow 10% below it, and you get the step factor. At 50:1, it is 1.48, so each 10% of travel adds about 48% to whatever the valve is passing. At 100:1, it is 1.58. Spirax prints the same 48% and 58%.

That’s the property a controller cares about. A linear trim gives a loop whose gain collapses as flow rises. An equal percentage trim roughly holds gain constant across the stroke, which is why these loops tune easily and stay stable over a wider band. That stability is what you’re buying, and it’s wasted when the load doesn’t need it.

Control Valve Flow Characteristics: Linear, Equal Percentage and Quick-Opening

Control Valve Flow Characteristics: Linear, Equal Percentage and Quick-Opening
Control Valve Flow Characteristics: Linear, Equal Percentage and Quick-Opening

Three names appear in every catalogue. A fourth and fifth exist and matter occasionally.

Curve Shape At 50% travel (inherent) Typical duty
Linear Flow proportional to travel 50% of capacity Level control, constant-drop mixing, plain flow loops
Equal percentage Logarithmic, R^(x−1) 14% at 50:1, 10% at 100:1 Coils, heat exchangers, steam, oversized valves
Quick opening Steep at the start, then flat Up to 90% of capacity On/off, relief, switching, two-position duty
Modified parabolic Between linear and equal % About 35% Legacy trims for specific pressure profiles
Hyperbolic and square-root Tuned to a drop relationship Varies Specialist sizing cases

A linear characteristic is the simplest to describe, and the one most people assume they want. Spirax notes in the same tutorial that linear valves suit water systems while steam systems tend to operate better with equal percentage. That sentence is worth more than most articles on the subject, because it names water and steam as two different load problems.

Quick opening is the one to be careful with. Spirax states plainly that, unlike linear and equal percentage, the exact shape of the fast-opening curve is not defined in standards. Two valves sold under that name can differ, and a lift of 50% may already pass up to 90% of capacity. It’s a switch in a valve body, and it belongs on duties meant to be switched.

Modified parabolic survives mainly on older installations. Treat it as a curve to identify, not one to specify new.

To obtain a detailed comparison, please see our article on throttling valve vs control valve.

Inherent vs Installed: Why the Catalogue Curve Does Not Arrive on Site

The table above is the inherent valve characteristic, measured on a bench at constant differential pressure. That is a clean, repeatable test and rarely describes a real installation.

On site, the pressure drop available to the valve falls as flow rises, for two reasons. Pipes, fittings, and coils downstream lose pressure in proportion to the square of flow. And a centrifugal pump’s head falls as flow increases. The valve therefore has the least pressure exactly when it’s wide open and needs the most.

The result is the installed characteristic, which is what you commission. The rule of thumb is blunt: an installed linear curve comes to resemble quick opening, and an installed equal percentage curve comes to resemble linear. Both are true within a band, and the band is narrower than the rule implies.

The Crossover Depends on Valve Authority

Valve authority is the fraction of the total loop pressure drop the valve owns at full flow. High authority means the valve controls most of the drop. Low authority means the rest of the system does, and the valve’s share shrinks as flow rises.

Authority Lift for 50% flow, linear Lift for 50% flow, equal % Flow at 50% lift, linear Flow at 50% lift, equal %
0.8 46% 80% 54% 16%
0.5 38% 75% 63% 20%
0.3 30% 69% 73% 25%
0.2 25% 65% 79% 30%

Model output: constant supply pressure, external losses proportional to flow squared, ideal trims, rangeability 50, flow normalised to 1.0 at full travel.

Three things fall out of that table.

First, the equal-percentage trim doesn’t become linear. It moves toward linear, and how far depends on authority.

Second, the linear trim degrades far more severely. At authority 0.2, it passes 79% of full flow at half travel, so the top half of its stroke is nearly useless and the resolution squeezes into the first quarter. That’s the mechanism behind the “linear valve hunts” complaint, and it’s a sizing problem wearing a trim costume.

Third, the authority you assume is often not the authority you have. A coil designed for a 30 kPa drop, in a loop that later gained a balancing valve and a long secondary run, is operating well below the number in the schedule.

For a deeper look, please read our article on valve authority explained.

The Selection Rule the Standards Give

ISA publishes a quantitative rule that turns this from judgment into arithmetic. Calculate the valve pressure drop decay, the ratio of valve drop at maximum flow to valve drop at minimum flow, and read the characteristic off the result:

  • Linear: 0.60 to 1.0
  • Modified parabolic: 0.35 to 0.60
  • Equal percentage: 0.20 to 0.35
  • Below 0.20: review the pipework, not the trim

ISA’s own wording is worth keeping in view: there should be a minimum of 0.20 decay to reach a reasonably linear control loop. Below that floor, no trim rescues the loop, because the valve no longer has enough pressure to steer. Our rangeability guide covers the related question of how wide the usable band is once you are inside it.

Matching the Equal Percentage Valve to the Load

Matching the Equal Percentage Valve to the Load
Matching the Equal Percentage Valve to the Load

This is where the standard advice and a plain reading of the catalogues part company, and where most specifying errors begin.

A water coil doesn’t deliver heat in proportion to water flow. Its output rises quickly at low flow and flattens as the water side stops being the limiting resistance, so the load curve bends.

Feed a bending load with a straight valve and the loop gain changes across the stroke. Feed it with a curve that is convex in flow and the product of the two flattens into something a controller can hold. That’s the entire engineering case for equal percentage on a coil, and it’s a statement about the load, not the valve.

A plain flow loop has no such bend. The controlled variable is flow, the load curve is the valve curve, and the exponential shape buys nothing while costing usable travel at the bottom of the stroke.

Why the Authorities Disagree

Béla Lipták, writing in Control Global, takes the strongest position:

“In my experience = % valves are the wrong selection flow control application. I use = % valves only for heat transfer control and use linear valves for regular flow control and quick opening for square root type flow control.”

His arithmetic in the same answer lands on the same ground as the table above. On a trim where each step adds a fixed percentage, he notes that “if today you operate at 50% of maximum flow, then your lift today should be about 80%”.

Spirax takes a softer line: linear for water, equal percentage for steam. ISA sidesteps the argument and asks you to compute the decay first.

These aren’t three opinions about one question. They describe three different loads.

Lipták is talking about flow control, where the load is flat. Spirax is talking about steam and heat exchange, where it isn’t. ISA is telling you to measure which situation you’re in before choosing.

Where Each Curve Wins

Choose linear when Choose equal percentage when
Three-port mixing or diverting, where the circuit holds the differential steady A two-port coil or AHU branch sits behind a pump curve
The branch is short and high-authority The duty is steam or a heat-exchanger temperature loop
The controlled variable is flow itself The valve is deliberately oversized
The differential is wide and stable, so the exponential curve would waste half the stroke The terminal is a chilled-water or hot-water unit, the common building case

Illustrative example, not a customer case study. Names are placeholders. A district-heating substation is fitted with equal-percentage trims on its three-port mixing valves because the specification says “differential pressure varies”. The circuit is a mixing loop that holds its differential reasonably steady. The valves do almost nothing for the first third of their stroke and everything in the last third, and the actuators hover near the top all winter. The trims are not defective. They answer a question this load was not asking.

Retrofits, Positioners and the BMS Trend Trap

Changing the Characteristic Without Buying a Valve

Trim swap. On most globe designs, Valin notes that the valve can be changed from linear to equal percentage, or back, by changing the trim. In other words, an equal percentage valve trim can replace the linear one in the valve already installed. On a ball valve, the port shape carries the characteristic, which is what a characterised port does; our page on the V-port ball valve covers that geometry.

Positioner characterisation. ISA notes that positioners can typically transform a linear characteristic into modified parabolic or equal percentage, or the reverse. That’s useful when the available trims don’t include what the load needs. It’s a correction layer, not a substitute for a correct valve.

Control-system remapping. A BMS can apply a curve to its output. This is the weakest of the three, because it moves the problem into the controller and leaves the valve’s usable band exactly as it was.

The BMS Trend Trap: 50% Position Is Not 50% Flow

A building management system will display four numbers that all read as a percentage: controller demand, commanded position, measured travel, and measured flow. On an equal-percentage trim, they diverge sharply at mid-stroke, and an operator reading the wrong one draws the wrong conclusion.

At authority 0.5, an equal-percentage trim at 50% travel passes about 20% of full flow. A linear trim in the same loop at the same travel passes about 63%. Both trends read “50%”. One coil is nearly starved; the other is nearly satisfied.

The practical rule is short. If you are diagnosing a coil from a trend, trend the flow or the temperature difference across it, not the valve position. Position tells you where the actuator is, not what the coil is getting.

Illustrative example, not a customer case study. Names are placeholders. A commissioning engineer finds an air-handling unit that will not reach setpoint with the drive at 55%. He replaces the actuator and nothing changes. The actuator was working. The trim had been selected for a duty with a very different load curve, and no actuator moves a curve.

What No Curve Will Fix

Be clear about the limits, because the trim is often blamed for problems it can’t touch.

  • Authority below the ISA floor. If the decay is under 0.20, fix the pipework or resize the valve.
  • A grossly oversized valve. Equal percentage tolerates oversizing better than linear, but does not cure it.
  • Cavitation, flashing, or a valve pinned in its last 5% of travel. These are hydraulic and sizing problems.
  • Hysteresis and dead band. These belong to the actuator, linkage, and positioner.

For a detailed comparison, please see our article on globe valve vs ball valve.

Equal Percentage Valve Options in Black Ant’s Range

Equal Percentage Valve Options in Black Ant's Range
Equal Percentage Valve Options in Black Ant’s Range

Black Ant manufactures both types this choice is about, and the trim names are published on the product pages rather than inferred.

The HVA electric regulating ball valve offers equal percentage as its main characteristic, with linear and quick opening also available. The ball core carries a “W” profile that produces the curve, which is the ball-valve equivalent of a characterised plug. The published specification covers a 100:1 turndown, sizes DN15 to DN300, PN16, a maximum closing differential of 1200 kPa, media from −20 to 120 °C, and control by 4-20mA, RS485 or M-Bus.

The electric control globe valve lists linear and equal percentage among its available characteristics, with leakage of 0 to 0.01% and a body rated to PN25. The electric ball valve range lists all three trims alongside IP65 protection and 50 to 5000 N·m of torque.

What the site doesn’t publish is a Cv or Kvs table for each size. That’s deliberate: the characteristic of a specific valve depends on its trim and its size together, and a table on a category page invites the wrong number into a schedule. Need the number for a schedule? Get the datasheet and the trim → and if you want to know what a Cv means, our guide to how Cv is calculated walks through it.

For a coil or air-handling branch, an equal-percentage trim on either body is the natural fit. For a three-port mixing circuit that holds its differential steady, specify linear. For isolation, quick opening, or, in truth, a standard ball valve rather than a regulating one. The electric control globe valve page carries its pressure and temperature envelope, and the HVA regulating ball valve page carries torque and signal options.

Specifying the Characteristic: Checklist and Three Mistakes

Six lines remove most of the guesswork.

  1. Duty: throttling or on/off. If it is on/off, specify a switch and stop.
  2. Required characteristic and the reason: name the load type, not just the curve.
  3. Pressure drop at maximum and minimum flow: the input for the decay check.
  4. Target authority and the basis for it.
  5. The valve’s share of the total loop drop at design flow.
  6. Actuator signal and fail position.

The three mistakes we see most often:

  • Choosing the curve before the sizing. A curve corrects a load; it can’t correct a valve that’s the wrong size.
  • Specifying equal percentage “because it is better”. It is better for a curved load and worse for a flat one.
  • Using positioner characterisation to hide an authority problem. You get a workable trend and an unchanged valve.

Frequently Asked Questions

What is the difference between an equal percentage valve and a linear valve?
A linear valve passes flow in proportion to travel at constant pressure drop. An equal percentage valve passes flow in proportion to a constant percentage per step of travel, so it moves far less flow at mid-stroke and catches up near full open.

How do you calculate the flow through an equal percentage valve?
Use Q/Qmax = R^(x − 1), where x is fractional travel, and R is the rangeability. At a 50:1 trim and 50% travel, the answer is about 0.14, or 14% of full flow.

Why is an equal percentage valve used for steam?
Because a steam heat exchanger presents a curved load, and the exponential trim linearises it. Spirax recommends linear for water systems and equal percentage for steam.

Can I make a linear valve behave like an equal percentage valve?
Sometimes. On most globe designs, a different trim will do it; a characterised ball port achieves it by geometry, and a positioner can reshape the curve electronically. None of them fixes a valve with too little authority.

What is the difference between rangeability and flow characteristic?
Rangeability is how wide a band of flow the valve can control. The characteristic is the shape of the curve through that band. A valve can have a wide band and a poor curve, or a good curve and a narrow band.

The Curve Is the Answer to a Question About the Load

An equal percentage valve isn’t the better valve. It’s the valve that answers a curved load, and the arithmetic is simple enough to check on paper.

The installed curve is the one that matters, and it depends on how much of the loop’s pressure drop the valve owns. At high authority, the equal-percentage trim keeps most of its shape. At low authority, it drifts toward linear, and the linear trim in the same loop collapses toward quick opening.

So the selection isn’t a preference. Decide whether your load is curved, measure how much drop the valve actually owns, and pick the curve that matches. If both checks come out unclear, that’s the conversation worth having before the valve is ordered. Send us the duty and the loop → and we will work through the decay and the trim with you.