Control Valve Leakage Classes: ANSI/FCI 70-2 Class I to VI Explained
A valve leakage class is the maximum amount of fluid a closed control valve is allowed to pass, proven by a defined test under defined conditions. ANSI/FCI 70-2 sets six of them, from Class I to Class VI. Class VI is the tightest, not Class I.
Classes II, III, and IV allow 0.5%, 0.1%, and 0.01% of rated capacity. Classes V and VI allow absolute rates set by seat diameter.
The direction of that scale is where most published tables go wrong. Search for a leakage class chart, and you’ll find pages calling Class I “the tightest shutoff available” and giving Class VI as “0.001 in³/min”. Both statements contradict the standard they cite.
The cause is that the six classes aren’t on one scale. Three are a fraction of a flow figure that changes with valve size. Two are fixed rates per inch of seat. Treat them as a single ladder, and you’ll specify the wrong valve, or accept the wrong test report.
This guide gives you the classes as the Fluid Controls Institute writes them, the arithmetic that makes them comparable, and the wording to put on a purchase order. From a comprehensive perspective, the electric valve selection guide covers body type, torque, characteristic, and leakage class.
If you’re holding two quotes for the same line and the shutoff numbers don’t line up, send both to our application engineers, and we’ll tell you what each one actually promises.
Key Takeaways
- The scale runs from Class I, which requires no test by agreement, up to Class VI, the tightest. Class I is the least documented, not the most.
- Classes II to IV scale with rated capacity, so the same class permits far more leakage on a larger valve. Classes V and VI scale with seat diameter.
- Class VI permits a tabulated rate: 0.15 ml/min at a 1-inch seat, up to 28.4 ml/min at 400 mm. It is an allowance, not zero.
- A metal-to-metal seat normally reaches Class IV. Class VI almost always needs a resilient seat and a temperature limit.
- A class describes a test. FCI 70-2 cannot predict leakage at other conditions, and its foreword points isolation duty at API 598.
What a Valve Leakage Class Actually Specifies

A class bundles three things: a limit, a test medium, and a test procedure. Change any one and the number means something else.
ANSI/FCI 70-2 was formerly ASME B16.104, adopted in November 1970. The current edition is ANSI/FCI 70-2-2021. The tables quoted here are from the 2006 edition, which is the text most widely circulated and the one whose numbers appear on most datasheets.
The standard defines four test procedures, and each class names the one it uses:
- Type A: clean air or water at 10 to 51°C, at 3 to 4 bar or within 5% of maximum operating differential, whichever is less. Full normal closing thrust, and no allowance is made for a lower test pressure.
- Type B: clean water, within 5% of maximum service pressure drop.
- Type B1: air or nitrogen at 3.5 barg inlet.
- Type C: air or nitrogen at maximum rated differential or 3.5 bar, whichever is less.
Two clauses in the standard matter more than any table.
The first is §2.2: “The standard cannot be used as a basis for predicting leakage at conditions other than those specified.” A valve that passes Class IV on a bench at 50 psig of clean water has not been promised anything at 180°C steam with a scaled seat. It has been promised that it passed a test.
The second is §3.3, which defines rated capacity as the quantity of test fluid that would pass at rated travel under the stated pressure conditions. That definition is the hinge of everything below.
The standard also states in §2.3 that it is similar to IEC 60534-4 “except that no provision is made for Class IV-S1”. That single absence explains why a European schedule and a US schedule can name different classes for the same duty.
For a detailed comparison, please see our article on butterfly valve vs. gate valve.
The Six Classes, Class by Class
The table below reproduces the limits and the construction each valve leakage class is normally associated with, in the standard’s own wording.
| Class | Maximum seat leakage | Measured against | Test | Normally associated with |
|---|---|---|---|---|
| I | By agreement | No limit stated | None | A modification of Class II, III or IV where no test is required |
| II | 0.5% | Rated valve capacity | Type A | Commercial double-seat and balanced single-seat with piston ring, metal-to-metal seats |
| III | 0.1% | Rated valve capacity | Type A | The Class II construction, with a higher degree of seat and seal tightness |
| IV | 0.01% | Rated valve capacity | Type A | Commercial unbalanced single-seat and tight balanced single-seat, metal-to-metal seats |
| V | 5 × 10⁻⁴ ml/min per inch of seat diameter per psi | Seat diameter and differential | Type B or B1 | Critical duty closed for long periods at high differential, metal seat, special assembly and testing |
| VI | Tabulated ml/min | Seat diameter | Type C | Resilient seating, unbalanced or balanced single-seat with O-rings or similar gapless seals |
Class I deserves a paragraph of its own, because it is the most misreported row. It isn’t a tightness level. It’s a documentation choice: a Class II, III or IV valve whose design intent is unchanged, but where user and supplier agree that no test is required.
A supplier quoting “Class I” has told you nothing about leakage. It has told you there will be no test result.
Class V is the first class that stops using percentage. Its limit is 5 × 10⁻⁴ millilitres per minute of water, per inch of seat diameter, per psi of differential. On a 2-inch seat at 100 psi, that’s 0.1 ml/min. For Type B1 testing, the standard gives an air equivalent: 4.7 standard ml per minute per inch of orifice diameter.
The Arithmetic Behind Every Valve Leakage Class

Here is the fact that no competing page states plainly. Rated capacity is a flow figure, and Cv is a coefficient. They aren’t the same number, and confusing them is why two people can read the same valve leakage class and disagree about what it allows.
The METRUS white paper on leakage calculation puts it directly: “The Cv (or KvS) is NOT the ‘rated valve capacity’ mentioned in 60534-4 Chapter 5.5.4 Table 3.” Rated capacity is the flow the valve would pass at 100% open under the test conditions. Cv is an input to calculating it.
Work one example. A valve with a rated Cv of 40, tested on water at a 50 psi differential, passes about 283 US gallons per minute wide open. That figure is its rated capacity for the test.
Class IV allows 0.01% of it, which is 0.028 gpm, or roughly 107 ml/min. That’s about 6.4 litres per hour.
Now put the same valve in Class V on a 2-inch seat at the same 50 psi. The limit is 5 × 10⁻⁴ × 2 × 50, which is 0.05 ml/min. Class V is more than two thousand times tighter on this valve, yet IV is the lower number on the scale.
That isn’t a paradox. It’s the difference between a proportional limit and an absolute one. Class IV says “a small fraction of what this valve can pass”. Class V says “this much, full stop”.
An illustrative scenario, not a measured case. A plant buys a DN50 valve with a Class IV guarantee and a DN200 with the same guarantee, and assumes the second is equally tight at a larger size. On the bench, the DN200 passes more than ten times as much water, because its rated capacity is more than ten times larger. Both pass. Neither supplier misled anyone.
So Class IV is a weak guarantee on a large valve. If the duty is “keep this line closed”, a Class IV number on a DN200 body may permit litres per hour. Size the requirement against the valve, not the class name. The control valve sizing guide takes you through the Cv behind these numbers.
Class VI, the Tightest Valve Leakage Class
Class VI is the only one stated as a table lookup. The limit depends on nominal seat diameter, not on capacity, so there’s no arithmetic to do once you know the seat size.
| Nominal seat diameter | Maximum leakage (ml/min) | Bubbles/min |
|---|---|---|
| Under 25 mm (under 1″) | 0.15 | 1 |
| 38 mm (1.5″) | 0.30 | 2 |
| 51 mm (2″) | 0.45 | 3 |
| 64 mm (2.5″) | 0.60 | 4 |
| 76 mm (3″) | 0.90 | 6 |
| 102 mm (4″) | 1.70 | 11 |
| 152 mm (6″) | 4.00 | 27 |
| 203 mm (8″) | 6.75 | 45 |
| 250 mm (10″) | 11.1 | Not tabulated |
| 300 mm (12″) | 16.0 | Not tabulated |
| 350 mm (14″) | 21.6 | Not tabulated |
| 400 mm (16″) | 28.4 | Not tabulated |
Source: ANSI/FCI 70-2-2006, Table 2. Editions published later may differ above 8 inches.
Three details in that table are usually left out of copies.
The interpolation rule. If the seat diameter differs by more than 2 mm from a tabulated value, the standard allows interpolation assuming that leakage varies as the square of the seat diameter. A 100 mm seat sits between the 102 mm and 76 mm rows, and the scaling is quadratic.
The bubble column. Bubbles are a suggested alternative for flow measurement, using a 0.25-inch OD by 0.032-inch wall tube submerged 1/8 to 1/4 inch. The standard says other apparatus may be used, provided the count correctly reflects millilitres per minute. That is why bubble counts in different copies disagree.
The units and the fluid. Class VI is an air or nitrogen test. There’s no liquid procedure. METRUS states the consequence: “Leakage class VI … stipulates air or gas as the test fluid. There is no calculation for liquids at all.” A page offering a Class VI figure in litres per hour of water has been extrapolated.
Now the word that causes the most trouble. Bubble-tight is a trade term with no definition in the standard, and zero leakage isn’t a class at all. Class VI permits 4 ml/min on a 6-inch seat, which is 27 bubbles a minute. If a quotation offers “bubble-tight, zero leakage”, ask which class it’s tested to and at what differential pressure.
On editions: the 2006 table gives 11.1, 16.0, 21.6 and 28.4 ml/min at 10, 12, 14 and 16 inches. Other published tables give 11.5, 16.4, 20.4 and 27.0 for the same sizes. IEC 60534-4:2021 extended the range below 25 mm and above 400 mm, so when two suppliers disagree about the 12-inch limit, both may be quoting a real edition. Ask which one.
To learn more information, please read our article on normally open vs normally closed valves.
What Your Seat Can Actually Hold

The class a valve reaches is a manufacturing outcome, not a catalogue preference. Construction sets the ceiling. Metal-to-metal seats, lapped and well guided, normally reach Class IV. They can reach Class V with special assembly and testing. Class VI almost always needs a resilient seat: PTFE, EPDM, or a similar elastomer that deforms into the seat surface.
The trade-off is temperature and media compatibility. A soft seat that holds Class VI at 20°C may be outside its rating at 150°C steam.
Processing Magazine puts the distinction in operational terms: a standard metal plug on a metal seat “can, and should give the valve a tightness of closure that meets the ANSI/FCI 70-2 Standard for a Class IV shutoff”, while a metal plug against a soft seat “can provide as high as a Class VI shutoff”.
For building services, the decision comes down to one question: is a small continuous flow acceptable? A chilled-water coil isolation valve on Class IV will pass a few litres an hour on a larger body. Over a summer, that’s enough to keep a coil warm and keep a chiller cycling at night.
An illustrative scenario, not a measured case. A coil valve is specified Class IV because that’s the number on the schedule. In summer, the coil still warms with the valve closed, and the chiller runs at night. The valve isn’t faulty. Class IV on that valve allows a few litres per hour, and a few litres per hour across a coil is enough to matter.
Black Ant publishes leakage figures rather than class claims. The fan coil control valve range is stated at ≤0.01% of Kv value with a soft seal and ≤0.1% with a hard seal. The electric control globe valve range is published at 0 to 0.01%, for DN15 to DN150, PN25 and -20 to 220°C.
Those are manufacturer leakage statements. A percentage of Kv isn’t the same document as a class certificate, and we don’t present one as the other. If your specification requires a certified class, ask us for the test report before you order. The seat construction behind these figures is covered in single-seat and double-seat valve designs.
For more information, please read our article on cage-guided control valves.
How to Write a Valve Leakage Class Requirement
Most disputes about shutoff are specification disputes, not manufacturing ones. Two bidders can quote the same valve leakage class and mean different tests.
Put seven fields in the requirement:
| Field | What goes in it |
|---|---|
| Standard | ANSI/FCI 70-2, plus the edition year |
| Class | The class number, I to VI |
| Test medium | Clean water, air, or nitrogen |
| Differential | The pressure drop at test, in bar or psi |
| Flow direction | Over the plug or under it, as installed |
| Duration and method | Test time, and how leakage is measured |
| Report | What the supplier must deliver with the valve |
An illustrative scenario, not a measured case. Two bidders quote the same valve, the same class, and different prices. One is quoting a water test at maximum operating differential; the other a no-load bubble test. Nobody wrote down the test condition, so neither quote can be compared.
A seat leakage test report should show the valve identification, the standard and edition, the class, the test medium, and the applied differential. It should also carry the measured leakage, the pass or fail, and the date and operator. Without the differential pressure, the number isn’t interpretable.
Then there’s the question of whether FCI 70-2 is the right standard at all. The FCI’s own informational sheet opens bluntly: “Control valves are not isolation valves; they will leak.” The standard’s foreword goes further, recommending another standard such as API 598, where “line isolation and/or absolute tight shut-off is a normal expectation of the valve application”.
So the boundary is:
- ANSI/FCI 70-2 for control valves, modulating duty, a defined seat leakage class.
- API 598 for isolation and block valves. A different scope, and for soft-seated valves, a zero-leakage acceptance.
- ISO 5208 for line valves, graded by rate and scaled to DN. Rate A is not convertible to Class VI.
- IEC 60534-4, where a European schedule is in force. It adds Class IV-S1 at a factor of 5 × 10⁻⁶, twenty times tighter than Class IV.
- GB/T 4213-2024, 《气动控制阀》, for the Chinese market. It took effect on 1 July 2025, replacing the 2008 edition, and defines classes Ⅰ to Ⅵ, including Ⅳ-S1. Check the published text before quoting per-class figures from it.
If a line must hold pressure with the control valve closed, the reliable answer is a separate isolation valve, not a tighter class on a control valve. The standard’s authors say so, and it’s usually cheaper than a Class VI trim on a large body.
For a deep understanding, please read our article on valve torque and actuator sizing.
Frequently Asked Questions
What is the maximum leakage rate for a control valve?
It depends on the class and the size. Class IV allows 0.01% of rated capacity. Class VI allows 0.15 ml/min at a 1-inch seat up to 28.4 ml/min at 400 mm, on air or nitrogen.
Is Class VI the same as bubble-tight or zero leakage?
No. Class VI is a tabulated allowance from 0.15 to 28.4 ml/min depending on seat diameter. Bubble-tight is a trade term with no standard definition, and zero leakage is not a class.
Can a metal-seated valve reach Class VI?
Rarely and not reliably. Metal-to-metal seats normally reach Class IV, and Class V with special assembly. Class VI almost always requires a resilient seat such as PTFE or EPDM, which brings a temperature limit.
Why does the same class permit more leakage on a bigger valve?
Because Classes II to IV are a fraction of rated capacity, and rated capacity rises with valve size. A DN200 valve with the same class number can pass more than ten times the water of a DN50 valve and still pass.
What is Class IV-S1, and why is it not in FCI 70-2?
It is an IEC 60534-4 class at a factor of 5 × 10⁻⁶, twenty times tighter than Class IV. FCI 70-2 §2.3 states that no provision is made for it, which is why US and European schedules can name different classes for the same duty.
Should I specify ANSI/FCI 70-2 for an isolation valve?
No. The FCI recommends another standard such as API 598, where line isolation is the normal expectation. A control valve closed against pressure is not a block valve.
Conclusion
The six classes are three proportional limits, two absolute ones, and one documentation option. That isn’t a single ladder. Read the valve leakage class, then read what it’s measured against.
Class IV on a large valve may pass litres per hour. Class VI is a tabulated rate, not zero. A metal seat normally reaches Class IV, and Class VI almost always means a soft seat with a temperature limit. And a class describes a test at stated conditions, so those conditions belong on the purchase order beside it.
Get those four points right and most shutoff arguments dissolve before the valves arrive. The wider selection framework is in the electric valve guide.
If you’re writing a shutoff requirement for an HVAC or light industrial duty, or comparing quotes that name different classes, send us the datasheet and the operating conditions. Our application engineers will check the class against the published figures and tell you which one the duty actually needs.