Normally Open vs Normally Closed Valves: Fail Position Guide
A normally closed valve shuts when it loses power. A normally open valve opens when it loses power. That de-energized position, not the control signal, is what the word normally means, and it is the first thing to settle on any valve schedule.
Most specifying errors are not about understanding that sentence. They are about the next one: fail position is a separate property from control action, and the two get confused on drawings, submittals, and commissioning sheets. A normally closed valve wired to the wrong controller action opens as the room gets hotter, and nothing about the valve looks faulty afterward. This guide separates the terms readers conflate, gives a selection table by duty, and ends with the check that proves the position before handover.
Key Takeaways
- Normally open and normally closed describe the de-energized state; direct and reverse acting describe the response to the control signal. They are independent.
- Hot water coils are conventionally normally open and chilled water coils normally closed, with exceptions for preheat, domestic hot water, steam and changeover systems.
- On a three-way valve, the terms name the port open to the common port, usually A for normally closed, B for normally open and AB for common.
- Valve fail position is fixed at order on most motorized product, so it belongs on the schedule and should be proven by removing power.
What Normally Open and Normally Closed Actually Mean

Both terms describe the valve in its de-energized state: no supply voltage at the actuator, no control signal, and, for a pneumatic actuator, no air pressure. A normally closed valve blocks flow in that state, and energizing it opens the valve. A normally open valve passes flow, and energizing it closes the valve.
Nothing about the handle position or the season changes that. It describes what happens when stored energy runs out, which is the state the building will be in during a power failure, a fire trip, or a maintenance isolation. Every other condition is one the system was designed to hold.
If you already have a valve schedule in front of you, send it over, and we will check the fail position on each coil against the sequences before you order.
Fail Position Is Not Control Action
Three properties get called acting on a valve drawing, and they answer three different questions: where the valve goes with no power, whether the controller output rises or falls as the measured variable rises, and which powered state moves the actuator.
A direct-acting controller raises its output as the room warms; a reverse-acting controller lowers it. Which valve position that output should produce depends on the duty. On a heating coil, rising temperature should reduce flow, so the output falls, and the valve closes.
Pair a reverse-acting controller with a normally open heating valve, and you get the classic inverted loop. The room warms, the controller lowers its output, the normally open valve de-energizes, and it opens wider. The room heats faster. The valve never closes. The valve is not faulty; the schedule is.
| Property | Question it answers | Options | Where it lives |
|---|---|---|---|
| Fail position | Where does it go with no power? | Normally open, normally closed, fail in place | Valve and actuator datasheet, valve schedule |
| Control action | Which way does it respond to the measured variable? | Direct acting, reverse acting | Controller configuration, sequences of operation |
| Energize state | What does the actuator do when powered? | Energize to open, energize to close | Wiring diagram, terminal schedule |
Standard control terminology. Confirm against the manufacturer’s own definitions, which vary in how they use direct acting.
A submittal that shows the fail position in one column and the control action in another is already doing the most useful thing you can do on paper. The columns that stay blank are the ones that cause the fault.
The Same Word Means Something Else on an Actuator
Manufacturers also use direct and reverse acting for the relationship between stem travel and flow, a different axis again. On a globe valve, a direct-acting actuator pushes the plug down to close, while a reverse-acting body opens as the stem extends. One package can carry three uses of acting, so when you read a submittal, ask which one is meant.
Illustrative example, not a customer case study. A commissioning engineer on a four-pipe retrofit found every perimeter heating valve driving open as the room warmed. The valves were correct: normally open, as specified. The room controllers had shipped with their factory action, which suited a cooling valve. Twenty minutes in the controller settings fixed a fault logged three times as a valve fault.
Choosing Normally Open or Normally Closed for the Duty

The convention is simple: hot water control valves are normally open, and chilled water control valves are normally closed. Published project specifications state it in almost those words, often in a clause that also fixes the valve type.
“Hot water control valves shall be normally open” and “Chilled water control valves shall be … normally closed.”
In short, a fail-open valve is chosen where loss of flow is the danger, and a fail-closed valve where unwanted flow is. Any valve specified this way is a fail-safe valve in the ordinary sense: its safe state is defined, documented and tested.
Heating Coils Fail Open Because Water Freezes
A normally open heating valve keeps flow through the coil when the power fails. In a cold climate, a still coil in a plant room or perimeter wall freezes, splits, and floods the space below. The valve is not there to keep the building warm during an outage; it is there so the water keeps moving, and so a heating source still serving the loop can protect the coil.
Chilled Water Coils Fail Closed Because Condensate Does Not
A chilled water coil has the opposite hazard. Uncontrolled flow on a power failure produces condensation on a coil nobody is draining, in a space nobody is monitoring. Closing the valve also removes load from a loop whose pump may have stopped.
Preheat, Domestic Hot Water and Steam
Preheat coils are usually normally open, and the freeze argument is strongest there because a preheat coil sits upstream of everything else in the air handling unit. Domestic hot water and steam duties usually fail closed: an open steam valve on failure is a scald and overpressure risk, and an open domestic hot water valve is a scald risk with no compensating benefit.
Changeover Systems Invert the Rule
The exception that catches people is a four-pipe, single-coil changeover system, where one coil carries hot water in winter and chilled water in summer. If the two valves failed in opposite directions, a failure could admit hot and chilled water to the same coil at once. Both are therefore normally closed, with a dead band in the sequences so neither is open when the space is satisfied. That contradicts the hot-water rule and is correct in its own context.
| Duty | Fail position | De-energized result | Reason |
|---|---|---|---|
| Heating coil, perimeter | Normally open | Flow continues | Freeze protection |
| Preheat coil | Normally open | Flow continues | Freeze protection upstream of the unit |
| Chilled water coil | Normally closed | Flow stops | No uncontrolled cooling or condensate |
| Domestic hot water | Normally closed | Flow stops | Scald and overflow protection |
| Steam coil or heat exchanger | Normally closed | Flow stops | Scald and overpressure protection |
| Four-pipe changeover, single coil | Normally closed, both valves | Both stop | Prevents hot and chilled water mixing |
| Safety venting and relief | Normally open | Vents | Pressure cannot be trapped |
Design convention summarized. Sequences of operation and the project specification govern.
Three-Way Valves: Normally Open and Normally Closed Name a Port
On a two-way valve, the terms are unambiguous, because one flow path is open or closed. A three-way valve has three ports, and the terms describe the relationship between two of them: the common port, usually labeled AB or COM, and two end ports labeled A and B. On most products, A is normally closed to the common and B is normally open to the common. A mixing valve has two inlets and one common outlet; a diverting valve has one common inlet and two outlets.
“The bottom port of the mixing valve is normally open to the common port … typically labeled NO … The other port is normally closed to the common and is typically labeled NC.”
| Valve function | Common port | Normally open port | Normally closed port | De-energized flow path |
|---|---|---|---|---|
| Two-way | Not applicable | Single path open | Single path closed | Closed |
| Three-way mixing | Outlet, AB | Inlet B | Inlet A | B to AB |
| Three-way diverting | Inlet, AB | Outlet B | Outlet A | AB to B |
Typical labeling. Verify against the maker’s own port markings, because A and B are not identical across all manufacturers.
The Port Nobody Checks Is the Bypass
In a coil bypass arrangement, one three-way port feeds the coil, and the other bypasses it. Which one is normally open decides what the coil does on a power failure, and it is the detail most often left to the installer. Get it backwards, and the coil is bypassed every time the power drops, or receives full flow when the design wanted it isolated. The valve is installed correctly, and the port assignment is wrong.
Draw the normally open port in its physical position on the schematic rather than relabeling it, and confirm the marking convention at the submittal stage. Mixing and diverting use interchangeable bodies but are not interchangeable applications; that choice belongs to a different decision, covered in two-way versus three-way fan coil valves.
How the Fail Position Is Physically Built

The fail position is not a setting. It is a mechanical and electrical property of the actuator, and it comes in three forms.
Spring Return
Spring return stores energy in a compressed spring that drives the valve to its fail position when power or air pressure is lost. It is the most predictable mechanism, because the spring either works or visibly fails, and it does not degrade with age the way a battery does. The cost is torque: the motor compresses the spring on every stroke, so a spring return valve actuator is usually larger and slower than a power-open, power-close unit. The spring return and double-acting actuator comparison covers the mechanism in detail.
Capacitor and Battery Return
Capacitor and battery return drive to the fail position using stored electrical energy, which keeps the actuator smaller where space is tight. But stored energy ages: a capacitor loses capacitance and a battery loses capacity, so both must be proven at commissioning and re-proven on a maintenance schedule.
Fail in Place
Fail in place holds the last position when power or signal is lost, which suits processes where an unplanned change of flow is worse than a stuck valve. It is a legitimate third position, not a failure of the other two, and worth stating explicitly rather than leaving a reader to assume open or closed.
For detailed information, please see our article on valve positioner vs actuator.
Motorized and Solenoid Valves Get There Differently
Most searches on this topic land on solenoid content, where the principle is described correctly. The mechanism differs, and the difference matters when you are buying.
A solenoid valve uses an electromagnetic coil to move a plunger directly, and its fail position comes from a return spring built into the valve. Manufacturers build them either way: “normally closed, preventing pressurized media from flowing in the unenergized state; or normally open, allowing pressurized media to pass in the unenergized state,” and the same body can serve as a selector or a diverter depending on which port is piped where (three-way solenoid valve applications). A motorized valve uses a motor and gear train to turn or stroke a ball, butterfly, or globe closure, and its fail position comes from the actuator. The body has no opinion about which state is safe.
Two things follow for a buyer. A pilot-operated solenoid depends on line pressure to assist the change of state, so it will not reliably shift at low or zero differential; a direct-operated one will. And fail position is usually fixed at order rather than switchable on site, so on a motorized assembly it attaches to the actuator, and both specifications have to be read together. Where the actuator is pneumatic, the whole mechanism changes, and electric versus pneumatic valve actuation is the right comparison.
For a terminal unit, the usual answer is a fan coil control valve with a normally open or normally closed actuator, where a compact body, a defined fail position and a short stroke matter more than a high flow coefficient.
Specifying and Proving the Fail Position

A fail position that is not written down, not matched to the controller, and not tested is a claim rather than a design decision. Five steps close the gap.
- Write the position into the sequences of operation. Name it per coil, not per valve type. A note that says only “fail safe” specifies nothing.
- Match the controller action to the position. For a normally open heating valve, confirm the pairing gives a closing action on rising temperature.
- Carry the position onto the schedule and the submittal. The schedule column, the product code, and the actuator datasheet must state the same position. A submittal listing two positions has not been checked.
- Confirm the terminal and wiring convention, as set out in wiring an electric control valve.
- Remove the power and watch. Isolate the actuator supply with the system live and observe the valve reach its fail position within the rated time. Record what you saw.
Step five is the only one that proves anything. The other four establish intent. If the power-off test is not on the commissioning schedule yet, send us the valve schedule, and we will flag which coils need it before handover.
Illustrative example, not a customer case study. A winter power failure in a building whose coil valves had all been specified normally closed produced frozen perimeter coils before anyone reached the plant room. The valves had done exactly what the schedule said. The schedule had specified the opposite of the design intent, and nobody had removed the power at handover to find out.
To learn more information, please read our article on control valve leakage classes.
Frequently Asked Questions
What is a normally closed valve and how does it work?
A normally closed valve blocks flow when it has no power and opens when the actuator is energized. The position is defined by the de-energized state, which is what the valve does during a power failure, a fire trip, or an isolation.
What does NC mean on a valve?
NC means normally closed: the valve is closed with no supply voltage at the actuator, and energizing it opens it. NO means normally open; the reverse. Both describe the state with stored energy exhausted, not the state during normal running.
Should a heating valve be normally open or normally closed?
A heating coil valve is conventionally normally open, so the coil keeps receiving flow during a power failure and does not freeze. The exception is a changeover system, where both valves are normally closed to prevent hot and chilled water mixing.
Is normally open the same as reverse acting?
No. Fail position describes what the valve does with no power; control action describes whether the controller output rises or falls as the measured variable rises. A normally open valve can be paired with either action, and the pairing decides whether the loop controls or runs away.
On a three-way valve, which port is normally open?
Port B is typically the port normally open to the common port, usually labeled AB or COM, and port A is typically normally closed. Labeling varies between manufacturers, so confirm against the port markings on the product.
How do you test a valve’s fail position?
Isolate the actuator supply with the system live and watch the valve move. Confirm it reaches the intended open, closed, or in-place position within the rated actuation time, and record the result.
Getting the Fail Position Right Before the Order
Normally open and normally closed say one thing: where the valve goes when the power is gone. Everything else on the schedule is about how it behaves when the power is on.
Treat the position as a property of the duty, not a preference. Heating coils open, chilled water coils closed, changeover systems closed on both sides, and the sequences override the convention wherever the hazard is different. Keep the position separate from control action on every document that carries it, because that is the pairing that fails quietly. Then prove it at commissioning by removing the power, which is the only test that answers the question the specification asked.
The electric valve selection guide covers where the fail position sits among the other decisions, including torque, flow characteristic, and shut-off class. If you have a schedule that needs a fail position confirmed, or a submittal that lists two, send it over, and we will check it against the sequences.